How Does CT Burden Affect Current Transformer Accuracy?

Posted by Claire

CT burden is an important factor in current transformer performance, but it is often overlooked when selecting or installing a CT. The secondary circuit does not only include the connected meter or relay. Cable resistance, terminals, connections, and other loads also contribute to the total burden.

When the actual burden becomes too high, the CT may no longer maintain its specified accuracy. This can increase ratio and phase errors and, under demanding conditions, contribute to saturation. As a result, the quality of the secondary current signal can affect both measurement and protection performance.

This article explains what CT burden means, how it is created and calculated, and how it affects CT accuracy. It also covers common sizing mistakes and key burden considerations for outdoor and renewable power applications.

LV CT WIRELESS TEMPERATURE SENSOR

1. What Is CT Burden?

CT burden describes the total load connected to a current transformer’s secondary circuit. It determines how much secondary-side demand the CT must supply and is an important part of matching a CT to its connected equipment.

CT Burden in VA and Ω

The burden can be expressed in VA or Ω, depending on how the secondary circuit is specified or calculated. For a mainly resistive circuit, the relationship is:

VA = I²×R

Because the current is squared, a 5A circuit produces 25 times the resistive loss of a 1A circuit with the same resistance.

Term Meaning
Rated burden Specified secondary load under the CT’s rated accuracy conditions
Actual burden Load created by the installed secondary circuit
VA Common unit for CT burden ratings and selection
Ω Used to express secondary-circuit impedance

Rated and actual burden should be distinguished during selection. Some CTs specify an accuracy range such as 25%-100% of rated burden. The applicable range depends on the CT specification.

2. What Creates CT Burden?

CT burden is the total secondary-circuit load, not simply the burden of the connected meter or relay. Several elements contribute to the load seen by the CT, so each part of the secondary circuit should be considered during selection and calculation.

Component What to Check
Meter/relay/transducer Rated burden
Secondary cable Length, conductor size, resistance
Terminals Contact and connection resistance
CT winding Manufacturer’s calculation method
Circuit Resistance and reactance

The actual burden depends on the complete secondary circuit. In practice, cable length and conductor size can become especially important when the CT is installed far from the connected equipment. The manufacturer’s specified calculation method should be followed when determining which internal CT losses are included.

3. How to Calculate Total CT Burden

The total burden should be calculated from the complete secondary circuit rather than one connected device.

Calculate the Actual Burden

List meter, relay, and other device burdens.

  • Calculate secondary cable resistance.
  • Convert cable resistance to VA using VA = I²×R
  • Add relevant terminal, connection, and winding contributions according to the manufacturer’s method.
  • Compare the total with the CT’s rated burden.

Check 1A vs 5A

A 5A secondary produces higher line losses than a 1A secondary. With the same resistance, its I²R loss is 25 times higher, making 1A suitable for many long secondary circuits. The final choice should match the connected equipment and CT specification.

Worked Example: A 5A CT with 1 Ω resistance has a 25 VA resistive burden. If rated at 15 VA, the actual burden is too high. Reducing resistance or using a suitable 1A secondary can lower the burden.

LV CT DROP STATUS INDICATOR

4. How CT Burden Affects Accuracy

CT burden affects how accurately a transformer reproduces primary current on its secondary side. As the secondary load increases, the CT requires more excitation current, which can increase measurement errors and reduce protection performance.

Condition Effect on CT Performance
Higher burden Increases excitation demand and may increase ratio error
Phase displacement Can affect metering and power measurement accuracy
High burden + fault current Increases the risk of core saturation
Saturation Distorts the secondary current waveform and may affect protection operation
Protection CT Check accuracy class, ALF, and knee-point requirements
Above rated burden Accuracy may exceed specified limits and saturation may occur
Within specified range CT operates under its specified accuracy conditions
Too low Accuracy may not be guaranteed, depending on the CT specification

Burden and Saturation: For protection applications, burden should be evaluated together with fault current and CT excitation characteristics. ALF, knee point, and accuracy class help determine whether the CT can reproduce current accurately under demanding conditions.

Too High or Too Low: For CTs specified with a 25%-100% rated-burden accuracy range, the actual burden should remain within that range unless the manufacturer specifies otherwise.

5. Common CT Burden Sizing Mistakes

Small errors in burden estimation can affect CT accuracy, especially in long secondary circuits or demanding protection applications.

Mistake Why It Matters What to Check
Counting only meters and relays Cable burden is missed Calculate the complete secondary load
Using 5A for a long circuit Higher I²R loss Consider 1A or larger conductors
Ignoring terminals Contact resistance is overlooked Check connections and terminals
Choosing excessive rated burden Actual load may fall outside the specified range Match rating to the calculated burden
Ignoring fault conditions Saturation risk may increase Check ALF, fault current, and knee point
Ignoring environment Resistance can vary with conditions Consider temperature, humidity, and installation conditions

Before selecting a CT, review the secondary circuit, accuracy class, burden, and operating conditions as one system rather than evaluating burden alone.

6. CT Burden in Outdoor and Renewable Power Projects

Outdoor transformer projects require more than a burden calculation. Environmental conditions can affect secondary-circuit resistance and connection reliability over time.

Factor Consideration
PV plants Long secondary cable runs
Transmission projects Extended circuit distances
Temperature Resistance changes with temperature
Humidity May affect insulation and connections
Salt spray Can accelerate connection degradation
Terminals Check contact condition and resistance

When CTs support metering or protection systems, consider burden, accuracy, installation conditions, and long-term operating reliability together.

LV CT CURRENT TRANSFORMER

Conclusion

CT burden is the total load of the secondary circuit, so accurate selection requires more than checking meter or relay burden. Secondary cable resistance, connections, CT specifications, and actual operating conditions all contribute to the final burden. A proper assessment helps control measurement errors and reduce the risk of saturation, supporting reliable metering and protection performance.

For outdoor transformer applications, CT selection should also account for temperature, humidity, installation conditions, and other environmental factors. CNMIBO supports outdoor transformer applications with attention to both electrical requirements and operating conditions. Need help with an outdoor transformer or CT-related application? Contact CNMIBO with your CT requirements, secondary-circuit details, installation conditions, and application requirements.