Current transformers (CTs) are essential components in modern electrical systems, providing accurate current measurement, electrical isolation, and protection support for power networks. They are widely used in substations, industrial facilities, renewable energy systems, switchgear, and energy monitoring applications.
When selecting a current transformer, engineers usually focus on several key specifications, including transformation ratio, accuracy class, rated burden, insulation level, and installation type. Among these parameters, accuracy and burden are two closely related factors that directly influence CT performance.
A current transformer with a high accuracy class cannot always maintain its rated performance if the connected burden exceeds its designed capacity. Therefore, understanding the relationship between current transformer accuracy vs burden is critical for choosing the right CT solution.
Whether selecting a window type current transformer, split core current transformer, Rogowski coil current transformer, or high voltage current transformer, proper matching between accuracy class and burden ensures reliable measurement and protection.

Current transformer accuracy refers to how precisely a CT converts the primary current into a proportional secondary current according to its rated transformation ratio.
Ideally, the secondary current should be an exact scaled-down version of the primary current. However, practical factors such as core losses, winding resistance, and magnetic characteristics can create small deviations.
CT accuracy mainly includes two types of errors:
Ratio Error
Ratio error is the difference between the actual transformation ratio and the rated transformation ratio.
For example, a CT with a ratio of 500/5A should output 5A when the primary current reaches 500A. Any difference between the actual output and the expected value creates a ratio error.
Phase Angle Error
Phase angle error refers to the difference in phase between the primary current and the secondary current.
This error is especially important in power measurement applications because it can affect:
For this reason, high-precision instrument current transformers are designed with optimized cores and winding structures to minimize errors.
The accuracy class indicates the maximum allowable error of a CT under specified operating conditions. Different applications require different accuracy levels.
| Accuracy Class | Type | Typical Applications | Main Characteristics |
| Class 0.1 | Metering CT | Laboratory measurement, precision testing | Extremely high measurement accuracy |
| Class 0.2 / 0.2S | Metering CT | Utility billing, revenue metering | High accuracy for commercial energy measurement |
| Class 0.5 / 0.5S | Metering CT | Industrial monitoring, energy management | Common accuracy level for industrial applications |
| Class 1.0 | Metering CT | General electrical measurement | Suitable for standard monitoring systems |
| 5P | Protection CT | Relay protection, substations | Maintains performance during fault conditions |
| 10P | Protection CT | General protection applications | Allows higher error for reliable protection operation |
Current transformers are generally divided into two categories: metering CTs and protection CTs.
Metering CTs
Metering CTs focus on measurement precision under normal operating conditions.
Typical applications include:
For these applications, accuracy classes such as 0.2, 0.5, and 1.0 are commonly used.
Protection CTs
Protection CTs are designed to maintain reliable output during abnormal conditions, such as short circuits and high fault currents.
They are commonly used in:
Protection CTs prioritize stability and saturation performance rather than extremely high measurement precision.

CT burden refers to the total load connected to the secondary winding of a current transformer.
It is usually measured in volt-amperes (VA) and represents the amount of electrical load that the CT needs to supply while maintaining its rated accuracy.
The total burden includes:
For example, a CT connected to a meter through a long cable will have a higher burden than the same CT connected with a short cable because cable resistance contributes to the total load.
A typical CT may have burden ratings such as:
The selected burden rating must be greater than the actual burden of the connected secondary circuit.
The relationship between accuracy and burden is one of the most important considerations when selecting a CT.
When the secondary burden increases, the CT needs to generate a higher secondary voltage to drive the connected load. This changes the magnetic operating condition of the core.
As burden increases:
As a result, the CT may no longer achieve its rated accuracy class.
For example, a Class 0.5 current transformer rated at 5VA burden may achieve its specified accuracy when connected to a 5VA load. However, if the actual secondary circuit burden increases beyond this value, measurement errors may exceed the allowable limit.
This is why engineers must evaluate the complete secondary circuit rather than only considering the CT itself.
The relationship between CT accuracy and burden can be summarized as follows:
| Parameter | Lower Burden | Higher Burden |
| Secondary voltage requirement | Lower | Higher |
| Core operating condition | More stable | Increased magnetic stress |
| Measurement error | Lower | Higher |
| Accuracy performance | Easier to maintain | May decrease |
| Risk of saturation | Lower | Higher, especially during faults |
| CT performance | Close to rated specification | May exceed accuracy limits |
A properly selected CT should operate within its rated burden range to maintain the expected accuracy class.
Selecting Incorrect Burden Rating
Choosing a CT with insufficient burden capacity can reduce measurement accuracy and affect system reliability.
Ignoring Secondary Cable Resistance
Long cable distances can significantly increase total burden.
Using the Wrong CT Type
A metering CT should not be used for protection applications, and a protection CT may not provide the precision required for billing measurement.
Choosing Accuracy Without Considering Application
Higher accuracy does not always mean better performance. The correct selection depends on the actual operating conditions and system requirements.

The relationship between current transformer accuracy and burden is fundamental to reliable electrical measurement and protection. Accuracy class defines how precisely a CT performs, while burden determines whether the CT can maintain that accuracy under actual operating conditions.
By selecting the correct accuracy class, burden rating, and CT design, engineers can ensure stable measurement performance, improved safety, and longer equipment service life.
From window type current transformers and split core current transformers to high voltage current transformers and instrument transformer solutions, choosing the right CT specifications is essential for modern power systems.
Mibo Electric is a professional transformer manufacturer specializing in current transformers, voltage transformers, instrument transformers, and electrical measurement solutions. With expertise in low-voltage, medium-voltage, and high-voltage applications, Mibo Electric provides reliable products for power systems, substations, renewable energy, industrial automation, and energy management projects worldwide.
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.