Follow Us:

CNMIBO CNMIBO CNMIBO CNMIBO CNMIBO
HIGH VOLTAGE CURRENT TRANSFORMER
HIGH VOLTAGE CURRENT TRANSFORMER

HIGH VOLTAGE CURRENT TRANSFORMER

Applicable working conditions

◆ Altitude: ≤1500m (Please indicate height above sea level if it is used in highland area)

◆ambient temperature:5℃ ~40℃.(If there any requirement,please indicate in the order)

◆relative humidity:≤85%

◆The installation site is free from gases,vapors,chemical deposits,dust,dirt and other explosive and corrosive media that seriously affect the insulation of the transformer,and there is no severe vibration or jolting.

Precautions

◆While the primary current goes through current transformer,the open circuit of secondary winding is not allowed,other wise high voltage will produce and affect the performance of product. 

◆The short circuit of secondary winding of voltage transformer is not allowed,otherwise the transformer will be burned.

◆The repeated power frequency withstand voltage test of primary winding shall be conducted under 80% of stipulated test vol

认证图标 认证图标 认证图标 认证图标 认证图标

Product Features

  • Application scenarios
    Indoor
  • Highest voltage for equipment
    24KV
  • Rated primary current
    20~1200A
  • Accuracy
    0.2S,0.5S,0.2,0.5,10P10,10P15
  • Rated secondary output
    10~20VA
  • Structure
    Casting type
Download

Technical data

Rated primary current(A) Accuracy classes combination Rated secondary output(VA)
0.2(S) 0.5 10P10 10P15
20-150 0.2(S)/0.2 0.2(S)/0.5 0.2(S)/10P10 0.5(S)/10P10 0.2(S)/10P15 0.5(S)/10P15 10 15 15 15
200
300-500
600  800 15 20 20 15
1000 1200